1. Mandatory Inspection Items
(Non‑compliance = direct rework)
- All metal cable trays (steel, galvanized, aluminum alloy) must be equipped with PE protective grounding.
- Grounding points:
- Total length ≤ 30 m: ≥ 2 grounding points (one at each end).
- Total length > 30 m: add one grounding point every 20–30 m.
- Grounding connection is mandatory at entries/exits of distribution boxes, cabinets, and electrical rooms.
- The entire length must form a continuous electrical path; no broken, insulated, or non‑conductive sections are allowed.
2. Connection and Bonding Standards
① Galvanized Cable Tray
- Each end of the joint plate shall have ≥ 2 bolts with lock washers or lock nuts.
- Contact surfaces must be clean (no paint, plastic, or debris) to ensure metal‑to‑metal conductivity.
- No jumper wire required.
② Spray‑painted, baked‑enamel, non‑galvanized tray
- Jumper bonding is required at both ends of each connection.
- Jumper: copper core flexible wire ≥ 4 mm².
- Paint/coating must be removed at bonding points to expose bare metal.
③ Deformation joints / expansion joints
- Must use flexible jumpers (typically braided copper wire ≥ 16 mm²).
- Ensure grounding continuity during thermal expansion, contraction, or structural settlement.
3. Grounding Resistance Standard
- Protective grounding resistance ≤ 4 Ω.
- When shared with lightning protection grounding: ≤ 1 Ω.
- Must be verified on‑site using a ground resistance tester.
4. Continuity Inspection (Critical for Inspection)
- Test with multimeter (resistance range).
- Between any two segments and between tray and main grounding bar:
- Continuity must be reliable, resistance near 0 Ω.
- No high resistance or open circuit allowed.
5. Appearance and Installation Standards
- Grounding connections firm, no looseness or missing parts.
- Jumpers neatly routed, not taut, twisted, or crushed.
- Grounding conductors must be yellow‑green.
- Supports and hangers shall be equipotentially bonded to the tray.
- No breaks in grounding continuity at wall or floor penetrations.
6. Acceptance Conclusion (Simplified Pass Criteria)
The installation is qualified if:
- Metal cable tray is continuously grounded along its entire length.
- Number of grounding points ≥ 2, with additional points for long runs.
- Galvanized tray: double bolts + locked; non‑galvanized: 4 mm² jumpers + paint removal.
- Entire system shows good electrical continuity.
- Grounding resistance ≤ 4 Ω.
- Deformation joints equipped with flexible jumpers.